The 45° offset rule
With two 45° fittings, the travel (centre to centre) is the offset × 1.414, and the run equals the offset. A 10 in offset needs 14.14 in of travel; a 250 mm offset needs 354 mm. Subtract the take-out of each fitting, and any root gaps, to get the pipe to cut.
45° long-radius elbow take-outs
| Pipe size | 90° LR take-out (in) | 45° LR take-out (in) | 90° LR (mm) | 45° LR (mm) |
|---|---|---|---|---|
| 1 in (DN 25) | 1 1/2 | 7/8 | 38 | 22 |
| 2 in (DN 50) | 3 | 1 3/8 | 76 | 35 |
| 3 in (DN 80) | 4 1/2 | 2 | 114 | 51 |
| 4 in (DN 100) | 6 | 2 1/2 | 152 | 64 |
| 5 in (DN 125) | 7 1/2 | 3 1/8 | 191 | 79 |
| 6 in (DN 150) | 9 | 3 3/4 | 229 | 95 |
| 8 in (DN 200) | 12 | 5 | 305 | 127 |
| 10 in (DN 250) | 15 | 6 1/4 | 381 | 159 |
| 12 in (DN 300) | 18 | 7 1/2 | 457 | 191 |
| 1/2 in (DN 15) | 1 1/2 | 5/8 | 38 | 16 |
| 3/4 in (DN 20) | 1 1/8 | 7/16 | 29 | 11 |
| 1-1/4 in (DN 32) | 1 7/8 | 1 | 48 | 25 |
| 1-1/2 in (DN 40) | 2 1/4 | 1 1/8 | 57 | 29 |
| 2-1/2 in (DN 65) | 3 3/4 | 1 3/4 | 95 | 44 |
A worked example
A 2 in line has to jog 10 in. Travel = 10 × 1.414 = 14.14 in. Each 2 in 45° LR elbow takes out 1-3/8 in, so subtract 2.75 in; with a 1/16 in root gap at each weld, subtract another 1/8 in. Cut the pipe to 11.27 in, or about 11-1/4 in.
These calculators do the arithmetic only. Check every measurement and cut before you make it, and follow the drawings, the code and the engineer of record for anything that carries pressure or load.