How to use it
Enter the offset depth and choose the bend angle. Add the distance from the end of the conduit to the obstruction to get both marks, with the shrink already allowed for.
Multiplier and shrink chart
| Bend angle | Multiplier | Shrink per inch of offset | Distance between bends for a 6 in offset (in) | Shrink for a 6 in offset (in) |
|---|---|---|---|---|
| 10° | 5.76 | 0.087 in (about 1/16) | 34.55 | 0.52 |
| 22.5° | 2.61 | 0.199 in (about 3/16) | 15.68 | 1.19 |
| 30° | 2.00 | 0.268 in (about 1/4) | 12.00 | 1.61 |
| 45° | 1.41 | 0.414 in (about 7/16) | 8.49 | 2.49 |
| 60° | 1.15 | 0.577 in (about 9/16) | 6.93 | 3.46 |
Choosing the angle
Shallow bends (10° and 22.5°) pull easier and look neater on small offsets but need a long distance between bends. 30° is the usual choice: the multiplier is exactly 2, so the arithmetic is easy. 45° and 60° save length on deep offsets but make wire pulling harder; keep the total of all bends in a run within what the code allows between pull points.
These calculators do the arithmetic only. Check every measurement and cut before you make it, and follow the drawings, the code and the engineer of record for anything that carries pressure or load.