NEC Table 310.16 (30 °C ambient, up to three current-carrying conductors)
| Wire | Copper 60 °C | Copper 75 °C | Copper 90 °C | Aluminum 60 °C | Aluminum 75 °C | Aluminum 90 °C |
|---|---|---|---|---|---|---|
| 14 AWG | 15 | 20 | 25 | – | – | – |
| 12 AWG | 20 | 25 | 30 | 15 | 20 | 25 |
| 10 AWG | 30 | 35 | 40 | 25 | 30 | 35 |
| 8 AWG | 40 | 50 | 55 | 35 | 40 | 45 |
| 6 AWG | 55 | 65 | 75 | 40 | 50 | 55 |
| 4 AWG | 70 | 85 | 95 | 55 | 65 | 75 |
| 3 AWG | 85 | 100 | 115 | 65 | 75 | 85 |
| 2 AWG | 95 | 115 | 130 | 75 | 90 | 100 |
| 1 AWG | 110 | 130 | 145 | 85 | 100 | 115 |
| 1/0 AWG | 125 | 150 | 170 | 100 | 120 | 135 |
| 2/0 AWG | 145 | 175 | 195 | 115 | 135 | 150 |
| 3/0 AWG | 165 | 200 | 225 | 130 | 155 | 175 |
| 4/0 AWG | 195 | 230 | 260 | 150 | 180 | 205 |
| 250 kcmil | 215 | 255 | 290 | 170 | 205 | 230 |
| 300 kcmil | 240 | 285 | 320 | 195 | 230 | 260 |
| 350 kcmil | 260 | 310 | 350 | 210 | 250 | 280 |
| 400 kcmil | 280 | 335 | 380 | 225 | 270 | 305 |
| 500 kcmil | 320 | 380 | 430 | 260 | 310 | 350 |
Which column to use
Use the column for the lowest temperature rating in the circuit: the wire's insulation, the breaker and the equipment terminals. THHN is a 90 °C wire, but on a breaker rated for 75 °C it is limited to the 75 °C column. Equipment of 100 A or less is often rated 60 °C unless it is marked 75 °C. The 90 °C column is the starting point for derating.
Small conductors
NEC 240.4(D) limits the overcurrent device on 14 AWG copper to 15 A, 12 AWG to 20 A and 10 AWG to 30 A (aluminum 12 AWG to 15 A and 10 AWG to 25 A), whatever the table says.
Derating
With four to six current-carrying conductors in a raceway, multiply by 80%; with seven to nine, 70%; with ten to twenty, 50% (NEC 310.15(C)(1)). Ambient above 30 °C takes a further correction from Table 310.15(B)(1): at 40 °C, for example, a 90 °C wire is multiplied by 0.91 and a 75 °C wire by 0.88.
Figures follow NEC Table 310.16 and Chapter 9 Table 8. Check them against the code edition your jurisdiction has adopted, any correction and adjustment factors (ambient temperature, more than three current-carrying conductors), the equipment's terminal ratings and the local inspector. Electrical work is often required to be done or checked by a licensed electrician.