How to use it
Enter the voltage, the load in amps, the one-way length and the voltage drop you will accept (3% is usual for a branch circuit). Pick the terminal temperature rating of the breaker and equipment, which is 75 °C for most equipment over 100 A and often 60 °C below that. The result "smallest for drop and load" is the wire that meets both tests.
Two tests, the larger wire wins
A wire must carry the current without overheating (its ampacity) and deliver enough voltage at the far end (its drop). On short runs ampacity decides; on long runs drop does. A 30 A circuit can use 10 AWG copper at 50 ft, but needs 8 AWG at 150 ft to stay within 3% at 240 V.
Copper wire for common breakers (short runs)
| Breaker | Copper wire | Aluminum wire |
|---|---|---|
| 15 A | 14 AWG | 12 AWG |
| 20 A | 12 AWG | 10 AWG |
| 30 A | 10 AWG | 8 AWG |
| 40 A | 8 AWG | 6 AWG |
| 50 A | 6 AWG (75 °C: 8 AWG) | 4 AWG |
| 60 A | 6 AWG (75 °C) | 4 AWG (75 °C) |
| 100 A | 3 AWG (75 °C) | 1 AWG (75 °C) |
| 200 A | 3/0 (75 °C) | 250 kcmil (75 °C) |
The table assumes 60 °C terminations up to 50 A unless marked, no more than three current-carrying conductors, and an ambient of 30 °C. Dwelling services and feeders can use NEC 310.12, which allows smaller conductors for the main power feeder.
Figures follow NEC Table 310.16 and Chapter 9 Table 8. Check them against the code edition your jurisdiction has adopted, any correction and adjustment factors (ambient temperature, more than three current-carrying conductors), the equipment's terminal ratings and the local inspector. Electrical work is often required to be done or checked by a licensed electrician.