The smallest copper or aluminum wire that carries the load and keeps voltage drop within your limit over the run.

Voltage drop and wire size

Voltage drop for a copper or aluminum circuit, and the smallest wire that keeps the drop within your limit and carries the load.

How it is worked out

Drop = 2 × K × I × L ÷ CM for single phase and DC, and 1.732 × K × I × L ÷ CM for three phase. K is 12.9 for copper and 21.2 for aluminum (ohm-circular mils per foot at 75 °C), I is the load in amps, L the one-way length in feet and CM the wire's area in circular mils (NEC Chapter 9 Table 8). The suggested wire is the smallest whose drop is within your limit and whose NEC Table 310.16 ampacity at the terminal rating, capped for 14 to 10 AWG by NEC 240.4(D), carries the load. It ignores reactance, which matters for large conductors on AC.

How to use it

Enter the voltage, the load in amps, the one-way length and the voltage drop you will accept (3% is usual for a branch circuit). Pick the terminal temperature rating of the breaker and equipment, which is 75 °C for most equipment over 100 A and often 60 °C below that. The result "smallest for drop and load" is the wire that meets both tests.

Two tests, the larger wire wins

A wire must carry the current without overheating (its ampacity) and deliver enough voltage at the far end (its drop). On short runs ampacity decides; on long runs drop does. A 30 A circuit can use 10 AWG copper at 50 ft, but needs 8 AWG at 150 ft to stay within 3% at 240 V.

Copper wire for common breakers (short runs)

BreakerCopper wireAluminum wire
15 A14 AWG12 AWG
20 A12 AWG10 AWG
30 A10 AWG8 AWG
40 A8 AWG6 AWG
50 A6 AWG (75 °C: 8 AWG)4 AWG
60 A6 AWG (75 °C)4 AWG (75 °C)
100 A3 AWG (75 °C)1 AWG (75 °C)
200 A3/0 (75 °C)250 kcmil (75 °C)

The table assumes 60 °C terminations up to 50 A unless marked, no more than three current-carrying conductors, and an ambient of 30 °C. Dwelling services and feeders can use NEC 310.12, which allows smaller conductors for the main power feeder.

Figures follow NEC Table 310.16 and Chapter 9 Table 8. Check them against the code edition your jurisdiction has adopted, any correction and adjustment factors (ambient temperature, more than three current-carrying conductors), the equipment's terminal ratings and the local inspector. Electrical work is often required to be done or checked by a licensed electrician.