Voltage drop calculator

Volts and percent dropped over a run, the voltage at the load, and the smallest wire that keeps the drop in your limit.

Voltage drop and wire size

Voltage drop for a copper or aluminum circuit, and the smallest wire that keeps the drop within your limit and carries the load.

How it is worked out

Drop = 2 × K × I × L ÷ CM for single phase and DC, and 1.732 × K × I × L ÷ CM for three phase. K is 12.9 for copper and 21.2 for aluminum (ohm-circular mils per foot at 75 °C), I is the load in amps, L the one-way length in feet and CM the wire's area in circular mils (NEC Chapter 9 Table 8). The suggested wire is the smallest whose drop is within your limit and whose NEC Table 310.16 ampacity at the terminal rating, capped for 14 to 10 AWG by NEC 240.4(D), carries the load. It ignores reactance, which matters for large conductors on AC.

How to use it

Pick single or three phase and copper or aluminum, then enter the supply voltage, the load current and the one-way length of the run, from the panel to the load. Choose the wire size you plan to use. The answer gives the drop in volts and percent, the voltage left at the load, and the smallest wire that would stay within your limit.

How much drop is acceptable

The NEC's informational notes suggest no more than 3% on a branch circuit and 5% in total from the service to the farthest outlet. These are recommendations, not rules, except where a section such as 647.4 for sensitive electronic equipment makes them one. Motors, pumps and long runs to outbuildings are where drop causes trouble: a motor on low voltage draws more current and runs hot.

Longest copper run within 3%

Copper wireLoad (A)Longest run at 120 V (ft)Longest run at 240 V (ft)Drop per 100 ft at that load (V)
14 AWG1538769.42
12 AWG2046917.90
10 AWG3048977.46
8 AWG5046927.81
6 AWG65561136.39
4 AWG85691375.25
3 AWG100731474.90
2 AWG115811614.47
1 AWG130901804.01
1/0 AWG150981963.66
2/0 AWG1751062123.39
3/0 AWG2001172343.08
4/0 AWG2301282572.80

Each row uses the wire's own 75 °C rating as the load. At a lighter load the run can be longer in proportion: half the amps, twice the distance.

Example

A 30 A, 240 V load 150 ft from the panel on 10 AWG copper drops 2 × 12.9 × 30 × 150 ÷ 10,380 = 11.2 V, or 4.7%. Going up to 8 AWG brings it to 7.0 V, or 2.9%.

Figures follow NEC Table 310.16 and Chapter 9 Table 8. Check them against the code edition your jurisdiction has adopted, any correction and adjustment factors (ambient temperature, more than three current-carrying conductors), the equipment's terminal ratings and the local inspector. Electrical work is often required to be done or checked by a licensed electrician.