How to use it
Pick the conduit type and trade size, then enter up to three wire sizes and how many of each. Count every conductor in the run, including the equipment ground. The answer gives the fill, the limit that applies, whether it passes, and the smallest size of that conduit that would.
The NEC fill rules
NEC Chapter 9 Table 1 limits the wires to 53% of the conduit's internal area for one wire, 31% for two, and 40% for three or more. The internal area depends on the conduit type: 1/2 in EMT has 0.304 in², while 1/2 in PVC schedule 40 has 0.285 in². A nipple of 24 in or less may be filled to 60%.
Usable area at 40%
| Trade size | EMT 40% (in²) | RMC 40% (in²) | PVC 40 40% (in²) | EMT total (in²) |
|---|---|---|---|---|
| 1/2 in | 0.122 | 0.126 | 0.114 | 0.304 |
| 3/4 in | 0.213 | 0.220 | 0.203 | 0.533 |
| 1 in | 0.346 | 0.355 | 0.333 | 0.864 |
| 1-1/4 in | 0.598 | 0.610 | 0.581 | 1.496 |
| 1-1/2 in | 0.814 | 0.828 | 0.794 | 2.036 |
| 2 in | 1.342 | 1.363 | 1.316 | 3.356 |
| 2-1/2 in | 2.343 | 1.946 | 1.878 | 5.858 |
| 3 in | 3.538 | 3.000 | 2.907 | 8.846 |
| 3-1/2 in | 4.618 | 4.004 | 3.895 | 11.545 |
| 4 in | 5.901 | 5.153 | 5.022 | 14.753 |
Fill is not the only limit
Passing on fill does not mean the pull is easy or that the wires can carry their full rating. More than three current-carrying conductors in one raceway means derating the ampacity (NEC 310.15), long runs and many bends need pulling lubricant and pull points, and no run may have more than 360° of bends between pull points.
Figures are from NEC Chapter 9 Tables 1, 4 and 5 for THHN/THWN-2 copper building wire. Check them against the code edition your jurisdiction has adopted, and against the local inspector, before you pull.