Amps to watts calculator

Watts and volt-amps from amps, or amps from watts, for DC, single phase and three phase.

Amps to watts

Watts and volt-amps from amps, or amps from watts, for DC, single-phase and three-phase circuits.

How it is worked out

Watts = volts × amps × power factor for DC and single phase, and 1.732 × volts × amps × power factor for three phase, with the line-to-line voltage. Volt-amps are the same without the power factor. Amps = watts ÷ (volts × power factor), or ÷ (1.732 × volts × power factor) for three phase. A power factor of 1 suits heaters and incandescent lamps; motors are usually 0.8 to 0.9.

How to use it

Pick the circuit type and enter the voltage and current. For a motor or other inductive load, enter its power factor from the nameplate (0.8 to 0.9 is typical); leave 1 for heaters and lamps. To go the other way, enter watts in the last box and the calculator gives the amps it draws.

Amps to watts at common voltages (power factor 1)

Amps120 V208 V240 V480 V three phase
1 A120 W208 W240 W831 W
5 A600 W1,040 W1,200 W4,157 W
10 A1,200 W2,080 W2,400 W8,314 W
15 A1,800 W3,120 W3,600 W12,471 W
20 A2,400 W4,160 W4,800 W16,628 W
30 A3,600 W6,240 W7,200 W24,942 W
40 A4,800 W8,320 W9,600 W33,255 W
50 A6,000 W10,400 W12,000 W41,569 W

Breakers and continuous loads

A breaker should carry no more than 80% of its rating for a load that runs three hours or more (NEC 210.20(A)). A 20 A, 120 V circuit has 2,400 W available but about 1,920 W for a continuous load such as a space heater.