pipefittercalc

Wire gauge chart

AWG sizes from 4/0 to 30 with diameter, mm², circular mils and copper resistance, and the ampacity of building wire.

Voltage drop and wire size

Voltage drop for a copper or aluminum circuit, and the smallest wire that keeps the drop within your limit and carries the load.

How it is worked out

Drop = 2 × K × I × L ÷ CM for single phase and DC, and 1.732 × K × I × L ÷ CM for three phase. K is 12.9 for copper and 21.2 for aluminum (ohm-circular mils per foot at 75 °C), I is the load in amps, L the one-way length in feet and CM the wire's area in circular mils (NEC Chapter 9 Table 8). The suggested wire is the smallest whose drop is within your limit and whose NEC Table 310.16 ampacity at the terminal rating, capped for 14 to 10 AWG by NEC 240.4(D), carries the load. It ignores reactance, which matters for large conductors on AC.

AWG sizes

AWGDiameter (in)Diameter (mm)Area (mm²)Circular milsCopper Ω per 1,000 ft (20 °C)Copper Ω per km (20 °C)
4/00.460011.684107.219211,6000.04900.1608
3/00.409610.40585.029167,8060.06180.2028
2/00.36489.26667.431133,0770.07790.2557
1/00.32498.25153.475105,5350.09830.3224
10.28937.34842.40883,6930.12390.4066
20.25766.54433.63166,3710.15630.5127
30.22945.82726.67052,6350.19700.6464
40.20435.18921.15141,7410.24850.8152
50.18194.62116.77333,1020.31331.0279
60.16204.11513.30226,2510.39511.2961
70.14433.66510.54920,8180.49821.6344
80.12853.2648.36616,5100.62822.0610
90.11442.9066.63413,0930.79212.5988
100.10192.5885.26110,3830.99883.2770
110.09072.3054.1728,2341.2604.132
120.08082.0533.3096,5301.5885.211
130.07201.8282.6245,1782.0036.571
140.06411.6282.0814,1072.5258.285
150.05711.4501.6503,2573.18410.448
160.05081.2911.3092,5834.01513.174
170.04531.1501.0382,0485.06316.612
180.04031.0240.8231,6246.38520.948
190.03590.9120.6531,2888.05126.415
200.03200.8120.5181,02210.15233.308
210.02850.7230.41081012.80242.001
220.02530.6440.32664216.14352.962
230.02260.5730.25850920.35666.784
240.02010.5110.20540425.66884.213
250.01790.4550.16232032.367106.191
260.01590.4050.12925440.814133.904
270.01420.3610.10220251.466168.850
280.01260.3210.08116064.897212.916
290.01130.2860.06412781.834268.483
300.01000.2550.051101103.190338.550

Diameters are for a solid round conductor. Stranded wire of the same gauge has the same copper area but a slightly larger overall diameter. Every 3 gauges roughly halves the area, and every 6 gauges roughly halves the diameter.

Ampacity of building wire

WireCopper 60 °CCopper 75 °CCopper 90 °CAluminum 60 °CAluminum 75 °CAluminum 90 °C
14 AWG152025–––
12 AWG202530152025
10 AWG303540253035
8 AWG405055354045
6 AWG556575405055
4 AWG708595556575
3 AWG85100115657585
2 AWG951151307590100
1 AWG11013014585100115
1/0 AWG125150170100120135
2/0 AWG145175195115135150
3/0 AWG165200225130155175
4/0 AWG195230260150180205
250 kcmil215255290170205230
300 kcmil240285320195230260
350 kcmil260310350210250280
400 kcmil280335380225270305
500 kcmil320380430260310350

Gauge to mm²

Metric cable is sold by area. 14 AWG (2.08 mm²) is nearest 2.5 mm², 12 AWG (3.31 mm²) nearest 4 mm², 10 AWG (5.26 mm²) nearest 6 mm² and 8 AWG (8.37 mm²) nearest 10 mm². Metric and AWG ratings are not interchangeable; use the rating for the cable you install.

Figures follow NEC Table 310.16 and Chapter 9 Table 8. Check them against the code edition your jurisdiction has adopted, any correction and adjustment factors (ambient temperature, more than three current-carrying conductors), the equipment's terminal ratings and the local inspector. Electrical work is often required to be done or checked by a licensed electrician.