Conduit fill chart

How many THHN wires of one size fit in EMT, rigid and PVC conduit, 1/2 to 4 inch, by the NEC limits.

Conduit fill

Percent fill and the smallest conduit for a mix of THHN/THWN-2 wires, to the NEC Chapter 9 limits.

How it is worked out

Fill = total wire area ÷ the conduit's internal area. Wire areas are for THHN/THWN-2 from NEC Chapter 9 Table 5 and conduit areas from Table 4. The limit is 53% for one wire, 31% for two and 40% for three or more (Table 1). Count every conductor, grounds included. Other insulation types (XHHW, RHW, bare) have different areas, so this calculator does not apply to them.

EMT: most THHN/THWN-2 wires of one size

Wire (THHN)1/2 in3/4 in1 in1-1/4 in1-1/2 in2 in2-1/2 in3 in3-1/2 in4 in
14 AWG1222356184138241364476608
12 AWG916264561101176266347443
10 AWG51016283863111167219279
8 AWG3691622366496126161
6 AWG147121626466991116
4 AWG1247101628435671
3 AWG113681324364760
2 AWG113571120304051
1 AWG11145815222937
1/0 AWG01134712192532
2/0 AWG01123610162026
3/0 AWG0111358131722
4/0 AWG0011147111418

Rigid metal conduit (RMC)

Wire (THHN)1/2 in3/4 in1 in1-1/4 in1-1/2 in2 in2-1/2 in3 in3-1/2 in4 in
14 AWG1322366385140200309412531
12 AWG916264662102146225301387
10 AWG6101729396492142189244
8 AWG3691622375382109140
6 AWG147121627385979101
4 AWG1247101623364862
3 AWG113681420314153
2 AWG113571117263444
1 AWG11145812192533
1/0 AWG01134710162127
2/0 AWG0112368131823
3/0 AWG0111357111519
4/0 AWG001114691216

PVC schedule 40

Wire (THHN)1/2 in3/4 in1 in1-1/4 in1-1/2 in2 in2-1/2 in3 in3-1/2 in4 in
14 AWG1121346082135193299401517
12 AWG81525435999141218293377
10 AWG591527376289137184238
8 AWG3591621365179106137
6 AWG14611152637577799
4 AWG114791622354761
3 AWG113681319304051
2 AWG113571116253343
1 AWG01135812182532
1/0 AWG01134710152127
2/0 AWG0112368131722
3/0 AWG0111357111418
4/0 AWG001114691215

How the chart is worked out

Each figure is 40% of the conduit's internal area divided by one wire's area, rounded down, except that a result of x.8 or more rounds up (NEC Chapter 9 note 7). These are the same numbers as the NEC Annex C tables. For two wires the limit is 31%, and for one wire 53%. For wires of different sizes, add their areas and use the calculator above.

Figures are from NEC Chapter 9 Tables 1, 4 and 5 for THHN/THWN-2 copper building wire. Check them against the code edition your jurisdiction has adopted, and against the local inspector, before you pull.