Conduit fill
Percent fill and the smallest conduit for a mix of THHN/THWN-2 wires, to the NEC Chapter 9 limits.
How it is worked out
Fill = total wire area ÷ the conduit's internal area. Wire areas are for THHN/THWN-2 from NEC Chapter 9 Table 5 and conduit areas from Table 4. The limit is 53% for one wire, 31% for two and 40% for three or more (Table 1). Count every conductor, grounds included. Other insulation types (XHHW, RHW, bare) have different areas, so this calculator does not apply to them.
EMT: most THHN/THWN-2 wires of one size
| Wire (THHN) | 1/2 in | 3/4 in | 1 in | 1-1/4 in | 1-1/2 in | 2 in | 2-1/2 in | 3 in | 3-1/2 in | 4 in |
|---|
| 14 AWG | 12 | 22 | 35 | 61 | 84 | 138 | 241 | 364 | 476 | 608 |
| 12 AWG | 9 | 16 | 26 | 45 | 61 | 101 | 176 | 266 | 347 | 443 |
| 10 AWG | 5 | 10 | 16 | 28 | 38 | 63 | 111 | 167 | 219 | 279 |
| 8 AWG | 3 | 6 | 9 | 16 | 22 | 36 | 64 | 96 | 126 | 161 |
| 6 AWG | 1 | 4 | 7 | 12 | 16 | 26 | 46 | 69 | 91 | 116 |
| 4 AWG | 1 | 2 | 4 | 7 | 10 | 16 | 28 | 43 | 56 | 71 |
| 3 AWG | 1 | 1 | 3 | 6 | 8 | 13 | 24 | 36 | 47 | 60 |
| 2 AWG | 1 | 1 | 3 | 5 | 7 | 11 | 20 | 30 | 40 | 51 |
| 1 AWG | 1 | 1 | 1 | 4 | 5 | 8 | 15 | 22 | 29 | 37 |
| 1/0 AWG | 0 | 1 | 1 | 3 | 4 | 7 | 12 | 19 | 25 | 32 |
| 2/0 AWG | 0 | 1 | 1 | 2 | 3 | 6 | 10 | 16 | 20 | 26 |
| 3/0 AWG | 0 | 1 | 1 | 1 | 3 | 5 | 8 | 13 | 17 | 22 |
| 4/0 AWG | 0 | 0 | 1 | 1 | 1 | 4 | 7 | 11 | 14 | 18 |
Rigid metal conduit (RMC)
| Wire (THHN) | 1/2 in | 3/4 in | 1 in | 1-1/4 in | 1-1/2 in | 2 in | 2-1/2 in | 3 in | 3-1/2 in | 4 in |
|---|
| 14 AWG | 13 | 22 | 36 | 63 | 85 | 140 | 200 | 309 | 412 | 531 |
| 12 AWG | 9 | 16 | 26 | 46 | 62 | 102 | 146 | 225 | 301 | 387 |
| 10 AWG | 6 | 10 | 17 | 29 | 39 | 64 | 92 | 142 | 189 | 244 |
| 8 AWG | 3 | 6 | 9 | 16 | 22 | 37 | 53 | 82 | 109 | 140 |
| 6 AWG | 1 | 4 | 7 | 12 | 16 | 27 | 38 | 59 | 79 | 101 |
| 4 AWG | 1 | 2 | 4 | 7 | 10 | 16 | 23 | 36 | 48 | 62 |
| 3 AWG | 1 | 1 | 3 | 6 | 8 | 14 | 20 | 31 | 41 | 53 |
| 2 AWG | 1 | 1 | 3 | 5 | 7 | 11 | 17 | 26 | 34 | 44 |
| 1 AWG | 1 | 1 | 1 | 4 | 5 | 8 | 12 | 19 | 25 | 33 |
| 1/0 AWG | 0 | 1 | 1 | 3 | 4 | 7 | 10 | 16 | 21 | 27 |
| 2/0 AWG | 0 | 1 | 1 | 2 | 3 | 6 | 8 | 13 | 18 | 23 |
| 3/0 AWG | 0 | 1 | 1 | 1 | 3 | 5 | 7 | 11 | 15 | 19 |
| 4/0 AWG | 0 | 0 | 1 | 1 | 1 | 4 | 6 | 9 | 12 | 16 |
PVC schedule 40
| Wire (THHN) | 1/2 in | 3/4 in | 1 in | 1-1/4 in | 1-1/2 in | 2 in | 2-1/2 in | 3 in | 3-1/2 in | 4 in |
|---|
| 14 AWG | 11 | 21 | 34 | 60 | 82 | 135 | 193 | 299 | 401 | 517 |
| 12 AWG | 8 | 15 | 25 | 43 | 59 | 99 | 141 | 218 | 293 | 377 |
| 10 AWG | 5 | 9 | 15 | 27 | 37 | 62 | 89 | 137 | 184 | 238 |
| 8 AWG | 3 | 5 | 9 | 16 | 21 | 36 | 51 | 79 | 106 | 137 |
| 6 AWG | 1 | 4 | 6 | 11 | 15 | 26 | 37 | 57 | 77 | 99 |
| 4 AWG | 1 | 1 | 4 | 7 | 9 | 16 | 22 | 35 | 47 | 61 |
| 3 AWG | 1 | 1 | 3 | 6 | 8 | 13 | 19 | 30 | 40 | 51 |
| 2 AWG | 1 | 1 | 3 | 5 | 7 | 11 | 16 | 25 | 33 | 43 |
| 1 AWG | 0 | 1 | 1 | 3 | 5 | 8 | 12 | 18 | 25 | 32 |
| 1/0 AWG | 0 | 1 | 1 | 3 | 4 | 7 | 10 | 15 | 21 | 27 |
| 2/0 AWG | 0 | 1 | 1 | 2 | 3 | 6 | 8 | 13 | 17 | 22 |
| 3/0 AWG | 0 | 1 | 1 | 1 | 3 | 5 | 7 | 11 | 14 | 18 |
| 4/0 AWG | 0 | 0 | 1 | 1 | 1 | 4 | 6 | 9 | 12 | 15 |
How the chart is worked out
Each figure is 40% of the conduit's internal area divided by one wire's area, rounded down, except that a result of x.8 or more rounds up (NEC Chapter 9 note 7). These are the same numbers as the NEC Annex C tables. For two wires the limit is 31%, and for one wire 53%. For wires of different sizes, add their areas and use the calculator above.
Figures are from NEC Chapter 9 Tables 1, 4 and 5 for THHN/THWN-2 copper building wire. Check them against the code edition your jurisdiction has adopted, and against the local inspector, before you pull.