How to use it
Count the insulated conductors of each size that enter the box: each hot, neutral and traveller counts once, and so does a wire that passes straight through. Enter the number of equipment grounding conductors (the bare or green wires), the number of devices (a duplex receptacle, switch or GFCI on one yoke is one), whether the box has internal cable clamps, and any fixture studs. Pick your box or type the volume stamped inside it.
Volume per conductor (Table 314.16(B))
| Wire size | Volume per conductor |
|---|---|
| 6 AWG | 5.00 in³ |
| 8 AWG | 3.00 in³ |
| 10 AWG | 2.50 in³ |
| 12 AWG | 2.25 in³ |
| 14 AWG | 2.00 in³ |
| 16 AWG | 1.75 in³ |
| 18 AWG | 1.50 in³ |
What counts
| Item | Counts as |
|---|---|
| Each conductor entering the box | 1 at its size |
| Conductor passing through, unspliced | 1 at its size |
| Unbroken loop 12 in or longer | 2 at its size |
| Pigtail that stays in the box | 0 |
| Internal cable clamps (any number) | 1 at the largest conductor |
| Each fixture stud or hickey | 1 at the largest conductor |
| Each device yoke or strap | 2 at the largest conductor on it |
| Equipment grounds, up to 4 | 1 at the largest ground |
| Each ground beyond 4 | ¼ at the largest ground |
Metal box volumes (Table 314.16(A))
| Box | Volume |
|---|---|
| 4 × 1-1/4 in round or octagonal | 12.5 in³ |
| 4 × 1-1/2 in round or octagonal | 15.5 in³ |
| 4 × 2-1/8 in round or octagonal | 21.5 in³ |
| 4 × 1-1/4 in square | 18.0 in³ |
| 4 × 1-1/2 in square | 21.0 in³ |
| 4 × 2-1/8 in square | 30.3 in³ |
| 4-11/16 × 1-1/4 in square | 25.5 in³ |
| 4-11/16 × 1-1/2 in square | 29.5 in³ |
| 4-11/16 × 2-1/8 in square | 42.0 in³ |
| 3 × 2 × 1-1/2 in device | 7.5 in³ |
| 3 × 2 × 2 in device | 10.0 in³ |
| 3 × 2 × 2-1/4 in device | 10.5 in³ |
| 3 × 2 × 2-1/2 in device | 12.5 in³ |
| 3 × 2 × 2-3/4 in device | 14.0 in³ |
| 3 × 2 × 3-1/2 in device | 18.0 in³ |
| 4 × 2-1/8 × 1-1/2 in device | 10.3 in³ |
| 4 × 2-1/8 × 1-7/8 in device | 13.0 in³ |
| 4 × 2-1/8 × 2-1/8 in device | 14.5 in³ |
| 3-3/4 × 2 × 2-1/2 in masonry | 14.0 in³ |
| 3-3/4 × 2 × 3-1/2 in masonry | 21.0 in³ |
A worked example
A receptacle box fed by two 12/2 cables and one 12/3 cable has 7 insulated 12 AWG conductors (7 × 2.25 = 15.75 in³), three grounds (one allowance, 2.25), one receptacle (2 × 2.25 = 4.50) and internal clamps (2.25): 24.75 in³ in all. A 4 × 1-1/2 in square box (21.0 in³) is too small; a 4 × 2-1/8 in square box (30.3 in³) works. A plaster ring or extension ring adds the volume marked on it.
Plastic boxes and boxes not in the table are marked with their volume by the maker; use that figure. Local amendments can change the rules, so check with the inspector.
These calculators do the arithmetic only. Check every measurement and cut before you make it, and follow the drawings, the code and the engineer of record for anything that carries pressure or load.