Box fill calculator

How many cubic inches your wires, devices, clamps and grounds need under NEC 314.16, and the smallest box that holds them.

Box fill

The volume a box needs for its wires, clamps, devices and grounds under NEC 314.16, and whether your box is big enough.

How it is worked out

Each insulated conductor that enters the box counts once at its NEC Table 314.16(B) allowance: 14 AWG 2.00 in³, 12 AWG 2.25, 10 AWG 2.50, 8 AWG 3.00 and 6 AWG 5.00. A wire that runs through without a splice also counts once; pigtails that never leave the box do not count. Internal cable clamps, however many, count once at the largest conductor. Each fixture stud or hickey counts once at the largest conductor. Each yoke or strap holding a device counts twice at the largest conductor connected to it; this calculator uses the largest conductor in the box. Up to four equipment grounding conductors count once at the largest of them, and each one beyond four adds a quarter. Enter the volume marked on the box when it is not in the list; plaster rings, extension rings and raised covers add their marked volume.

How to use it

Count the insulated conductors of each size that enter the box: each hot, neutral and traveller counts once, and so does a wire that passes straight through. Enter the number of equipment grounding conductors (the bare or green wires), the number of devices (a duplex receptacle, switch or GFCI on one yoke is one), whether the box has internal cable clamps, and any fixture studs. Pick your box or type the volume stamped inside it.

Volume per conductor (Table 314.16(B))

Wire sizeVolume per conductor
6 AWG5.00 in³
8 AWG3.00 in³
10 AWG2.50 in³
12 AWG2.25 in³
14 AWG2.00 in³
16 AWG1.75 in³
18 AWG1.50 in³

What counts

ItemCounts as
Each conductor entering the box1 at its size
Conductor passing through, unspliced1 at its size
Unbroken loop 12 in or longer2 at its size
Pigtail that stays in the box0
Internal cable clamps (any number)1 at the largest conductor
Each fixture stud or hickey1 at the largest conductor
Each device yoke or strap2 at the largest conductor on it
Equipment grounds, up to 41 at the largest ground
Each ground beyond 4¼ at the largest ground

Metal box volumes (Table 314.16(A))

BoxVolume
4 × 1-1/4 in round or octagonal12.5 in³
4 × 1-1/2 in round or octagonal15.5 in³
4 × 2-1/8 in round or octagonal21.5 in³
4 × 1-1/4 in square18.0 in³
4 × 1-1/2 in square21.0 in³
4 × 2-1/8 in square30.3 in³
4-11/16 × 1-1/4 in square25.5 in³
4-11/16 × 1-1/2 in square29.5 in³
4-11/16 × 2-1/8 in square42.0 in³
3 × 2 × 1-1/2 in device7.5 in³
3 × 2 × 2 in device10.0 in³
3 × 2 × 2-1/4 in device10.5 in³
3 × 2 × 2-1/2 in device12.5 in³
3 × 2 × 2-3/4 in device14.0 in³
3 × 2 × 3-1/2 in device18.0 in³
4 × 2-1/8 × 1-1/2 in device10.3 in³
4 × 2-1/8 × 1-7/8 in device13.0 in³
4 × 2-1/8 × 2-1/8 in device14.5 in³
3-3/4 × 2 × 2-1/2 in masonry14.0 in³
3-3/4 × 2 × 3-1/2 in masonry21.0 in³

A worked example

A receptacle box fed by two 12/2 cables and one 12/3 cable has 7 insulated 12 AWG conductors (7 × 2.25 = 15.75 in³), three grounds (one allowance, 2.25), one receptacle (2 × 2.25 = 4.50) and internal clamps (2.25): 24.75 in³ in all. A 4 × 1-1/2 in square box (21.0 in³) is too small; a 4 × 2-1/8 in square box (30.3 in³) works. A plaster ring or extension ring adds the volume marked on it.

Plastic boxes and boxes not in the table are marked with their volume by the maker; use that figure. Local amendments can change the rules, so check with the inspector.

These calculators do the arithmetic only. Check every measurement and cut before you make it, and follow the drawings, the code and the engineer of record for anything that carries pressure or load.