How to use it
Pick single or three phase, enter the voltage and the load current, and read the kVA and the next standard transformer rating. Enter a kVA rating in the last box to see the full-load current it delivers at that voltage.
kVA to amps
Single phase: amps = kVA × 1,000 ÷ V. Three phase: amps = kVA × 1,000 ÷ (1.732 × V). A 75 kVA three-phase transformer at 480 V delivers 90.2 A; at 208 V it delivers 208.2 A.
Single-phase amps per kVA
| kVA | 120 V | 208 V | 240 V | 480 V |
|---|---|---|---|---|
| 5 | 41.7 A | 24.0 A | 20.8 A | 10.4 A |
| 10 | 83.3 A | 48.1 A | 41.7 A | 20.8 A |
| 15 | 125.0 A | 72.1 A | 62.5 A | 31.3 A |
| 25 | 208.3 A | 120.2 A | 104.2 A | 52.1 A |
| 37.5 | 312.5 A | 180.3 A | 156.3 A | 78.1 A |
| 50 | 416.7 A | 240.4 A | 208.3 A | 104.2 A |
| 75 | 625.0 A | 360.6 A | 312.5 A | 156.3 A |
| 100 | 833.3 A | 480.8 A | 416.7 A | 208.3 A |
| 167 | 1391.7 A | 802.9 A | 695.8 A | 347.9 A |
Standard transformer sizes
Single phase: 5, 10, 15, 25, 37.5, 50, 75, 100, 167, 250, 333, 500 kVA. Three phase: 15, 30, 45, 75, 112.5, 150, 225, 300, 500, 750, 1000, 1500, 2000, 2500 kVA. The suggestion is the next rating at or above the load you entered; the size you buy follows the calculated load under NEC Article 220, plus room for growth, and the primary and secondary protection follows NEC 450.3.
These calculators do the arithmetic only. Check every measurement and cut before you make it, and follow the drawings, the code and the engineer of record for anything that carries pressure or load.