The airflow a room needs for a given number of air changes an hour, and the airflow for an air conditioner's tonnage.

CFM and air changes

Airflow a room needs for a number of air changes an hour, and airflow from tons of cooling.

How it is worked out

CFM = room volume in cubic feet × air changes per hour ÷ 60. In metric, airflow in m³/h is the volume in m³ × air changes, and L/s is that ÷ 3.6. Typical rates run from 0.35 air changes an hour for whole-house fresh air (ASHRAE 62.2 sets a floor) to 6 to 10 for kitchens, bathrooms and workshops. A central air system moves about 400 CFM per ton of cooling, 350 in humid climates, so a 3-ton system needs about 1,200 CFM.

How to use it

Enter the room's length, width and ceiling height and the air changes per hour you want. The calculator gives the room volume and the airflow in CFM and litres a second. For an air conditioner or heat pump, enter the tons of cooling to see the airflow its blower should move.

The formula

CFM = length × width × height × air changes per hour ÷ 60. A 12 × 12 ft room with an 8 ft ceiling holds 1,152 ft³; six air changes an hour needs 115 CFM.

Typical air changes per hour

SpaceAir changes per hour
Whole house, fresh air0.35 or more
Bedroom, living room2 to 4
Bathroom6 to 8
Kitchen7 to 15
Workshop or garage4 to 6
Paint or finishing booth30 to 60
Server or equipment room15 to 20

CFM per ton

Central air systems are set up for about 400 CFM per ton of cooling: a 2-ton unit moves about 800 CFM, a 3-ton about 1,200 and a 5-ton about 2,000. In humid climates installers often set 350 CFM per ton so the coil removes more moisture. These are rules of thumb; the room-by-room airflow comes from an ACCA Manual J load calculation.

These calculators do the arithmetic only. Check every measurement and cut before you make it, and follow the drawings, the code and the engineer of record for anything that carries pressure or load.