How to use it
Enter the room's length, width and ceiling height and the air changes per hour you want. The calculator gives the room volume and the airflow in CFM and litres a second. For an air conditioner or heat pump, enter the tons of cooling to see the airflow its blower should move.
The formula
CFM = length × width × height × air changes per hour ÷ 60. A 12 × 12 ft room with an 8 ft ceiling holds 1,152 ft³; six air changes an hour needs 115 CFM.
Typical air changes per hour
| Space | Air changes per hour |
|---|---|
| Whole house, fresh air | 0.35 or more |
| Bedroom, living room | 2 to 4 |
| Bathroom | 6 to 8 |
| Kitchen | 7 to 15 |
| Workshop or garage | 4 to 6 |
| Paint or finishing booth | 30 to 60 |
| Server or equipment room | 15 to 20 |
CFM per ton
Central air systems are set up for about 400 CFM per ton of cooling: a 2-ton unit moves about 800 CFM, a 3-ton about 1,200 and a 5-ton about 2,000. In humid climates installers often set 350 CFM per ton so the coil removes more moisture. These are rules of thumb; the room-by-room airflow comes from an ACCA Manual J load calculation.
These calculators do the arithmetic only. Check every measurement and cut before you make it, and follow the drawings, the code and the engineer of record for anything that carries pressure or load.