Conduit size calculator

The smallest EMT, rigid or PVC conduit that holds your wires within the NEC fill limit.

Conduit fill

Percent fill and the smallest conduit for a mix of THHN/THWN-2 wires, to the NEC Chapter 9 limits.

How it is worked out

Fill = total wire area ÷ the conduit's internal area. Wire areas are for THHN/THWN-2 from NEC Chapter 9 Table 5 and conduit areas from Table 4. The limit is 53% for one wire, 31% for two and 40% for three or more (Table 1). Count every conductor, grounds included. Other insulation types (XHHW, RHW, bare) have different areas, so this calculator does not apply to them.

How to use it

Choose the conduit type, then enter each wire size and how many of it, grounds included. The calculator gives the smallest trade size that keeps the fill within the NEC Chapter 9 limit, and the fill of the size you picked.

Smallest EMT for common circuits (THHN, ground included)

WiresSmallest EMT
3 × 12 AWG1/2 in
4 × 12 + 1 × 12 ground1/2 in
9 × 12 AWG1/2 in
3 × 10 + 1 × 10 ground1/2 in
3 × 8 + 1 × 10 ground3/4 in
3 × 6 + 1 × 10 ground3/4 in
4 × 4 + 1 × 8 ground1-1/4 in
4 × 2 + 1 × 6 ground1-1/4 in
4 × 1/0 + 1 × 6 ground1-1/2 in
4 × 3/0 + 1 × 4 ground2 in
4 × 250 kcmil + 1 × 4 ground2-1/2 in

How conduit is sized

Add up the cross-section of every wire from NEC Chapter 9 Table 5, then pick the smallest conduit whose internal area from Table 4, times the fill limit, is at least that total. The limit is 40% for three or more wires, 31% for two and 53% for one (Table 1). A conduit nipple 24 in or shorter may be filled to 60%. Long runs and many bends pull harder, so a size up is common even when the fill passes; a run may have no more than 360° of bends between pull points.

These calculators do the arithmetic only. Check every measurement and cut before you make it, and follow the drawings, the code and the engineer of record for anything that carries pressure or load.