Duct size calculator

The round duct an airflow needs at your friction rate, the velocity it runs at, and a rectangular duct that matches it.

Duct size

Round duct diameter for an airflow and friction rate, the air velocity, and a rectangular duct that matches it.

How it is worked out

For galvanized round duct and standard air, the friction loss per 100 ft in inches of water is 0.109136 × CFM^1.9 ÷ D^5.02 (D in inches), the fit behind duct calculators and friction charts; the calculator solves it for D. Velocity = CFM ÷ area. A rectangular duct of sides a and b matches a round one of 1.30 × (a × b)^0.625 ÷ (a + b)^0.25 (the Huebscher equivalent), and the calculator finds the width for your height. Residential systems are usually laid out at 0.05 to 0.10 in. w.g. per 100 ft, with supply velocity under about 900 ft/min to stay quiet; flex duct needs a size or more larger. A full design uses ACCA Manual D.

How to use it

Enter the airflow in CFM and the friction rate in inches of water per 100 ft of duct; 0.08 to 0.10 is usual for home systems. The calculator gives the round duct diameter and velocity. To use rectangular duct, enter the height that fits the joist bay or ceiling and read the width.

CFM to round duct size (galvanized, 0.08 in. w.g. per 100 ft)

AirflowRound ductVelocity
50 CFM4.7 in (use 5 in)419 ft/min
100 CFM6.1 in (use 7 in)496 ft/min
150 CFM7.1 in (use 8 in)548 ft/min
200 CFM7.9 in (use 8 in)587 ft/min
300 CFM9.2 in (use 10 in)648 ft/min
400 CFM10.3 in (use 11 in)695 ft/min
600 CFM12.0 in (use 12 in)767 ft/min
800 CFM13.4 in (use 14 in)822 ft/min
1000 CFM14.5 in (use 15 in)868 ft/min
1200 CFM15.6 in (use 16 in)908 ft/min
1600 CFM17.4 in (use 18 in)973 ft/min
2000 CFM18.9 in (use 19 in)1027 ft/min

Rectangular equivalents

Round8 in high10 in high12 in high
8 in7 × 86 × 105 × 12
10 in11 × 89 × 108 × 12
12 in16 × 813 × 1011 × 12
14 in22 × 817 × 1014 × 12
16 in30 × 823 × 1019 × 12
18 in40 × 830 × 1024 × 12

A rectangular duct carries less air than its area suggests, because the corners add drag; the Huebscher equivalent-diameter formula accounts for that. Flex duct has two to three times the friction of metal duct, so size it up. Keep supply ducts in a home under about 900 ft/min and returns under about 700 to stay quiet; a full design follows ACCA Manual D.

These calculators do the arithmetic only. Check every measurement and cut before you make it, and follow the drawings, the code and the engineer of record for anything that carries pressure or load.