How to use it
Pick a steel pipe size to fill in its Schedule 40 bore, or type the inside diameter of copper, PEX or PVC. Enter the velocity to get the flow, or enter a flow to see how fast the water moves. For a tap, hose or well, time how long a bucket takes to fill.
The formula
GPM = 2.448 × ID² × velocity, with the inside diameter in inches and the velocity in feet per second. A 2 in Schedule 40 pipe (2.067 in bore) at 5 ft/s carries 52.3 GPM.
Flow by Schedule 40 pipe size
| Pipe | Bore | At 4 ft/s | At 5 ft/s | At 8 ft/s |
|---|---|---|---|---|
| 1/2 in | 0.622 in | 3.8 GPM | 4.7 GPM | 7.6 GPM |
| 3/4 in | 0.824 in | 6.6 GPM | 8.3 GPM | 13.3 GPM |
| 1 in | 1.049 in | 10.8 GPM | 13.5 GPM | 21.6 GPM |
| 1-1/4 in | 1.380 in | 18.6 GPM | 23.3 GPM | 37.3 GPM |
| 1-1/2 in | 1.610 in | 25.4 GPM | 31.7 GPM | 50.8 GPM |
| 2 in | 2.067 in | 41.8 GPM | 52.3 GPM | 83.7 GPM |
| 2-1/2 in | 2.469 in | 59.7 GPM | 74.6 GPM | 119.4 GPM |
| 3 in | 3.068 in | 92.2 GPM | 115.2 GPM | 184.3 GPM |
| 4 in | 4.026 in | 158.7 GPM | 198.4 GPM | 317.4 GPM |
| 6 in | 6.065 in | 360.2 GPM | 450.2 GPM | 720.4 GPM |
Plumbing codes and pipe makers usually limit water velocity to about 8 ft/s for cold water and 5 ft/s for hot, to avoid noise, water hammer and erosion of copper. Fixture flow and pipe sizing for a building follow the plumbing code's fixture-unit tables.
These calculators do the arithmetic only. Check every measurement and cut before you make it, and follow the drawings, the code and the engineer of record for anything that carries pressure or load.