kW, kVA and kVAR from line-to-line voltage, current and power factor, and the amps a three-phase load draws.
All 32 calculators
Three-phase power and kVA
kVA, kW and kVAR from voltage, current and power factor, the current a kVA rating draws, and the next standard transformer size.
How it is worked out
Three phase: kVA = 1.732 × V × I ÷ 1,000, with V the line-to-line voltage; single phase: kVA = V × I ÷ 1,000. kW = kVA × power factor, and kVAR = √(kVA² − kW²). Amps from a kVA rating = kVA × 1,000 ÷ (1.732 × V), or ÷ V for single phase. The transformer suggestion is the next standard rating at or above the load (ANSI C57.12 sizes); a real transformer is sized for the calculated load per NEC 220 and for future growth.
Amps to watts
Watts and volt-amps from amps, or amps from watts, for DC, single-phase and three-phase circuits.
How it is worked out
Watts = volts × amps × power factor for DC and single phase, and 1.732 × volts × amps × power factor for three phase, with the line-to-line voltage. Volt-amps are the same without the power factor. Amps = watts ÷ (volts × power factor), or ÷ (1.732 × volts × power factor) for three phase. A power factor of 1 suits heaters and incandescent lamps; motors are usually 0.8 to 0.9.
How to use it
Enter the line-to-line voltage (208, 240, 480 or 600 V in North America; 400 or 415 V in much of the world), the current in one line and the power factor. The calculator gives apparent power in kVA, real power in kW and reactive power in kVAR. To size a feeder from a rating, type the kVA and read the amps.
The formulas
Three-phase apparent power: kVA = √3 × V × I ÷ 1,000, where √3 ≈ 1.732. Real power: kW = kVA × power factor. Current from power: I = kW × 1,000 ÷ (1.732 × V × PF). The √3 appears because each line's current is shared between two phase voltages 120° apart. Use the line-to-line voltage, not line to neutral; with line to neutral (277 V on a 480 V system) the formula is 3 × V × I.
Amps per kVA, three phase
kVA
208 V
240 V
480 V
600 V
15
41.6 A
36.1 A
18.0 A
14.4 A
30
83.3 A
72.2 A
36.1 A
28.9 A
45
124.9 A
108.3 A
54.1 A
43.3 A
75
208.2 A
180.4 A
90.2 A
72.2 A
112.5
312.3 A
270.6 A
135.3 A
108.3 A
150
416.4 A
360.8 A
180.4 A
144.3 A
225
624.5 A
541.3 A
270.6 A
216.5 A
300
832.7 A
721.7 A
360.8 A
288.7 A
500
1387.9 A
1202.8 A
601.4 A
481.1 A
Power factor
Motors draw current that is out of step with the voltage, so the kVA a cable and transformer carry is larger than the kW that does work. A fully loaded induction motor runs at about 0.85; a lightly loaded one can fall to 0.5. Heaters run at 1. Utilities often bill large customers for low power factor, which capacitors correct.