Type K, L and M copper tube
| Nominal | OD (in) | Type K wall / ID (in) | Type L wall / ID (in) | Type M wall / ID (in) |
|---|---|---|---|---|
| 1/4 | 0.375 | 0.035 / 0.305 | 0.030 / 0.315 | — |
| 3/8 | 0.500 | 0.049 / 0.402 | 0.035 / 0.430 | 0.025 / 0.450 |
| 1/2 | 0.625 | 0.049 / 0.527 | 0.040 / 0.545 | 0.028 / 0.569 |
| 3/4 | 0.875 | 0.065 / 0.745 | 0.045 / 0.785 | 0.032 / 0.811 |
| 1 | 1.125 | 0.065 / 0.995 | 0.050 / 1.025 | 0.035 / 1.055 |
| 1-1/4 | 1.375 | 0.065 / 1.245 | 0.055 / 1.265 | 0.042 / 1.291 |
| 1-1/2 | 1.625 | 0.072 / 1.481 | 0.060 / 1.505 | 0.049 / 1.527 |
| 2 | 2.125 | 0.083 / 1.959 | 0.070 / 1.985 | 0.058 / 2.009 |
| 2-1/2 | 2.625 | 0.095 / 2.435 | 0.080 / 2.465 | 0.065 / 2.495 |
| 3 | 3.125 | 0.109 / 2.907 | 0.090 / 2.945 | 0.072 / 2.981 |
| 4 | 4.125 | 0.134 / 3.857 | 0.110 / 3.905 | 0.095 / 3.935 |
Dimensions are for copper water tube to ASTM B88. All three types of one size share the outside diameter, so they take the same fittings; the type sets the wall.
Which type
Type K has the thickest wall and is used underground and for services. Type L is the usual choice for water supply inside buildings, and Type M, the thinnest, is allowed for some residential supply and heating where the local plumbing code permits it. The tube is marked with a coloured print line: green for K, blue for L and red for M.
Copper tube size versus pipe size
Copper tube is named by nominal size, and its outside diameter is always 1/8 in larger: 1/2 in copper is 0.625 in outside. Refrigeration (ACR) tube is named by its actual outside diameter instead, so 5/8 ACR is the same tube as 1/2 nominal. Iron pipe sizes (NPS) are different again; the pipe schedule chart lists those.
These calculators do the arithmetic only. Check every measurement and cut before you make it, and follow the drawings, the code and the engineer of record for anything that carries pressure or load.