Copper pipe size chart

Outside diameter, wall and inside diameter of Type K, L and M copper tube, with the water volume and weight per foot.

Copper tube size

Outside and inside diameter, wall, water volume and weight per foot of Type K, L or M copper tube.

How it is worked out

Copper water tube to ASTM B88 has an outside diameter 1/8 in larger than its nominal size; the type sets the wall. Inside diameter = OD − 2 × wall. Water volume = π ÷ 4 × ID² × 12 ÷ 231 US gallons per foot. Weight = π × (OD − wall) × wall × 12 × 0.323 lb per foot, plain tube without fittings.

Type K, L and M copper tube

NominalOD (in)Type K wall / ID (in)Type L wall / ID (in)Type M wall / ID (in)
1/40.3750.035 / 0.3050.030 / 0.315—
3/80.5000.049 / 0.4020.035 / 0.4300.025 / 0.450
1/20.6250.049 / 0.5270.040 / 0.5450.028 / 0.569
3/40.8750.065 / 0.7450.045 / 0.7850.032 / 0.811
11.1250.065 / 0.9950.050 / 1.0250.035 / 1.055
1-1/41.3750.065 / 1.2450.055 / 1.2650.042 / 1.291
1-1/21.6250.072 / 1.4810.060 / 1.5050.049 / 1.527
22.1250.083 / 1.9590.070 / 1.9850.058 / 2.009
2-1/22.6250.095 / 2.4350.080 / 2.4650.065 / 2.495
33.1250.109 / 2.9070.090 / 2.9450.072 / 2.981
44.1250.134 / 3.8570.110 / 3.9050.095 / 3.935

Dimensions are for copper water tube to ASTM B88. All three types of one size share the outside diameter, so they take the same fittings; the type sets the wall.

Which type

Type K has the thickest wall and is used underground and for services. Type L is the usual choice for water supply inside buildings, and Type M, the thinnest, is allowed for some residential supply and heating where the local plumbing code permits it. The tube is marked with a coloured print line: green for K, blue for L and red for M.

Copper tube size versus pipe size

Copper tube is named by nominal size, and its outside diameter is always 1/8 in larger: 1/2 in copper is 0.625 in outside. Refrigeration (ACR) tube is named by its actual outside diameter instead, so 5/8 ACR is the same tube as 1/2 nominal. Iron pipe sizes (NPS) are different again; the pipe schedule chart lists those.

These calculators do the arithmetic only. Check every measurement and cut before you make it, and follow the drawings, the code and the engineer of record for anything that carries pressure or load.