How to use it
Enter a height of water to get the pressure it exerts, or a pressure to get the equivalent height. For another liquid, enter its specific gravity. To size a pump, enter the vertical lift from the water level to the outlet, the friction loss in the pipe (the friction loss calculator gives it in feet) and the pressure you need at the outlet.
Feet of water to psi
| Feet of water | psi | Feet of water | psi |
|---|---|---|---|
| 1 | 0.43 | 50 | 21.6 |
| 2 | 0.87 | 60 | 26.0 |
| 5 | 2.16 | 75 | 32.5 |
| 10 | 4.33 | 100 | 43.3 |
| 15 | 6.49 | 120 | 51.9 |
| 20 | 8.66 | 150 | 64.9 |
| 25 | 10.82 | 200 | 86.6 |
| 30 | 12.99 | 231 | 100.0 |
| 40 | 17.32 | 300 | 129.9 |
The rule of thumb
Every 2.31 ft of water height adds 1 psi, or 0.433 psi per foot. A tank 50 ft above a tap gives about 21.6 psi there with no flow; a well pump lifting from 100 ft must make 43 psi just to bring the water to the surface. Pressure depends only on height, not on the size or shape of the tank or pipe.
Pump head
A pump's total dynamic head is the sum of the static lift, the friction loss at the design flow, and the pressure needed at the outlet expressed as head. Read the pump curve at your flow: the pump must deliver at least this head there. Check the suction side separately: a pump can lift water only about 25 ft by suction at sea level, less when the water is warm or the site is high.
These calculators do the arithmetic only. Check every measurement and cut before you make it, and follow the drawings, the code and the engineer of record for anything that carries pressure or load.