How to use it
Enter the flow in gallons per minute and the pipe's actual inside diameter, which the copper and PVC charts list. Enter the length of the run, adding an equivalent length for the fittings, and pick the material. The calculator gives the pressure loss, the head loss in feet, the loss per 100 ft and the water velocity.
Pressure loss per 100 ft (psi)
| Pipe (ID) | 2 GPM | 5 GPM | 10 GPM | 15 GPM | 20 GPM | 30 GPM | 50 GPM |
|---|---|---|---|---|---|---|---|
| 1/2 copper L (0.545 in) | 3.3 | 18.3 | — | — | — | — | — |
| 3/4 copper L (0.785 in) | 0.6 | 3.1 | 11.2 | 23.7 | — | — | — |
| 1 copper L (1.025 in) | 0.2 | 0.8 | 3.0 | 6.5 | 11.0 | — | — |
| 1 PVC sch 40 (1.049 in) | 0.1 | 0.7 | 2.4 | 5.1 | 8.7 | — | — |
| 1-1/2 PVC sch 40 (1.61 in) | 0.0 | 0.1 | 0.3 | 0.6 | 1.1 | 2.3 | 5.9 |
| 2 PVC sch 40 (2.067 in) | 0.0 | 0.0 | 0.1 | 0.2 | 0.3 | 0.7 | 1.7 |
A dash means the velocity would be over 10 ft/s, too fast for that pipe.
Fittings
Each elbow, tee and valve adds loss. A common allowance is to add the length of straight pipe that loses the same: roughly 2 to 3 ft for a 3/4 in elbow and 4 to 5 ft for a tee through the branch, more for larger sizes. For a quick estimate, add 25 to 50% to the straight length of a run with many fittings.
Limits of the method
Hazen-Williams is the standard method for water in full pipes at ordinary temperatures. It is not for other liquids, hot water above about 140 °F, slurries or gases; use the Darcy-Weisbach method for those. Keep supply velocities under about 5 to 8 ft/s for quiet piping, and follow your plumbing code for sizing.
These calculators do the arithmetic only. Check every measurement and cut before you make it, and follow the drawings, the code and the engineer of record for anything that carries pressure or load.